FILM AND TELEVISION INSTITUTE OF INDIA
LAW COLLEGE ROAD, PUNE - 411 004.
| Telephone Exchange: |
25432299, 25431817,
25430363, 25430017 (Ext.210) |
Fax No. :
E-mail : |
91-020-25430416 purhcase@ftiindia.com |
| Purchase Officer : |
25431366 |
Date of Enquiry :
|
29/01/2011 |
| Tender Enquiry No. : |
PN / 124 |
Due Date : |
21/02/2011 |
| S.No. |
Particulars |
Details & Make |
| 1. |
Required capacity |
10 TR |
| 2. |
Media to be cooled |
Water |
| 3. |
Chiller outlet Temperature |
8 degree C. |
| 4. |
Refrigerant |
R22 |
| 5. |
Evaporator |
Shell & Tube type |
| 6. |
Condenser |
Water cooled |
| 7. |
Maximum Ambient Temperature |
40 degrees C. |
| |
TECHNICAL SPECIFICTIONS: - |
|
| 1. |
Cooling capacity required at application |
7.7 TR |
| 2. |
Pump load [ primary pump (2 HP) + secondary pump (2 HP) ] |
0.84 TR |
| 3. |
Leakage load (5%) + FOS (5%) |
0.85 TR |
| 4. |
Total cooling capacity |
9.41 TR |
| |
SPECIFICATIONS :- |
|
| 1. |
Compressor model |
Scroll compressor |
| 2. |
Condenser |
Water cooled, MS Shell & copper tube |
| 3. |
Evaporator |
Shell & Tube type, MS Shell & copper tube |
| 4. |
Expansion device |
Thermostatic- Danfoss/Alco make |
| 5. |
Refrigerant |
R 22 |
| 6. |
Electrical supply |
415 VAC + - 10%, 50 HZ, Three phase |
| 7. |
Refrigeration controls |
HPLP cut out, liquid line drier, sight glass, flow switch,pressure gauges,pressure relief valve. |
| 8. |
Electrical controls |
MCB,OLR. Temp.indicator cum controller,standard make temperature indicator cum controller,switchgear & indicators. |
| 9. |
Primary pump |
2 HP, KBL/Crompton make |
| 10. |
Secondary pump |
2 HP, KBL/Crompton make |
| 11. |
Water tank |
3000 ltrs., SS tank with 50 mm PUF insulation & MS structure for tank. |
| |
PART LIST: CHILLER :-
PART LIST 1 : -REFRIGERATION. (Chiller must have parts as above)- |
|
| 1. |
Compressor |
Scroll Compressor (01 no.) |
| 2. |
Condenser |
Water cooled, MS Shell & copper tube. (01 no.) |
| 3. |
Expansion device |
Thermostatic (01 no.) |
| 4. |
Evaporator |
Shell & Tube type, MS Shell & copper tube
(01 no.) |
| 5. |
Refrigerant |
R22 (lot) |
| 6. |
Refrigeration controlls |
- Timer,Indicators for flow switch & HPLP
- Pressure gauges with valves
- Solenoid valves
- Adjustable sight glass pressure cutout
- Liquid line drier
- Flow switch
- Pressure relief valve
- Temperature Controller
- Ante freeze Thermostat
- Accumulator
(FULL SET FOR ABOVE ) |
| |
ELECTRICAL AND MECHANICAL :-
|
|
| 1. |
Enclosure |
Powder coated MS structure for refrigeration circuit & electrical |
| 2. |
MCB-Compressor, control |
Siemens/equivalent |
| 3. |
Contactor – Compressor ,control |
Siemens/equivalent |
| 4. |
OLR-Compressor |
Siemens/equivalent |
| 5. |
Single phase Preventer |
Siemens/equivalent |
| 6. |
Switch - Compressor |
Teknik/equivalent |
| 7. |
Lamp- Compressor on |
Apexa/equivalent |
| 8. |
Lamp- R Y B |
Apexa/equivalent |
| 9. |
Temperature indicator cum controller |
- |
| |
OPERATING PARAMETERS / PROVISIONS REQUIRED FOR CHILLER :- |
|
| |
Capacity |
Nominal capacity of chiller is the nominal capacity of the compressor at ASRE/T conditions of
Ambient temperature – 35 degrees C.
Evaporating temp.- 7.2 degrees C
Sub cooled liquid temp.- 46.1 degrees C.
Condensing temp.- 55 degrees C.
Suction gas temp.- 35 degrees C. |
| |
PART LIST 2- CHILLED WATER CIRCUIT- |
|
| 1. |
Primary pump |
2 HP (01 no.) |
| 2. |
Secondary pump |
2 HP (01 no.) |
| 3. |
Electrical |
For pump – Contactor, MCB, OLR, indicating lamps, selector switch, (Siemens/equivalent)
(Set) |
| 4. |
Chilled Water Piping |
As per site location. (Set) |
| |
PART LIST 3 – CONDENSER WATER CIRCUIT - |
|
| 1. |
Cooling tower |
Advance make, total capacity 15 TR. (01 no.) |
| 2. |
Cooling tower pump |
5 HP, 2.52 LPS @ 40 m head (01 no.) |
| 3. |
Pump inlet & outlet valves |
Ball Valves (02 nos.) |
| 4. |
Electrical |
For pump – Contactor, MCB, OLR, indicating lamps, selector switch, (Siemens/equivalent)
(Set) |
| 5. |
Cooling Tower Piping |
As per site location |
|
( For more details contact- Shri Ayyathurai, Lab,Manager, Ext.No.- 278 )
The rates to be quoted should be inclusive of all taxes, including packing, freight charges and octroi charges for door delivery at our Stores at the FTII.
| |
Yours faithfully,
(S.K. Shahare)
Purchase Officer |
Note:
| 1) |
The vendor has to submit a Earnest Money Deposit (EMD) @2% of your quoted value in the form of Demand Draft in favor of Accounts Officer Film & TV Institute of India, Pune payable at Pune. In case vendor fails to submit the said EMD his quotation may be considered but he has to submit a performance security Deposit @ 5% of the Purchase Order Value if the said Vendor is a successful Bidder for the order. |
| 2) |
Mention Enquiry No, Name of the Material, Quotation No. & Due Date and write as ‘Limited Tender Enquiry ’ on the Envelope. |
| 3) |
Quotation by Fax / email and Conditional Quotation will not be accepted. |
| 4) |
Rates to be quoted in words & any correction/overwriting should stamped & signed. |
*TERMS AND CONDITIONS
|