Tender

FILM AND TELEVISION INSTITUTE OF INDIA
LAW COLLEGE ROAD, PUNE - 411 004.

Telephone Exchange: 25432299, 25431817,
25430363, 25430017 (Ext.210)
Fax No. :
E-mail :
91-020-25430416 purhcase@ftiindia.com
Purchase Officer : 25431366 Date of Enquiry : 29/01/2011
Tender Enquiry No. : PN / 124 Due Date : 21/02/2011
S.No. Particulars Details & Make
1. Required capacity

10 TR

2. Media to be cooled Water
3. Chiller outlet Temperature 8 degree C.
4. Refrigerant R22
5. Evaporator Shell & Tube type
6. Condenser Water cooled
7. Maximum Ambient Temperature 40 degrees C.
  TECHNICAL SPECIFICTIONS: -  
1. Cooling capacity required at application 7.7 TR
2. Pump load [ primary pump (2 HP) + secondary pump (2 HP) ] 0.84 TR
3. Leakage load (5%) + FOS (5%) 0.85 TR
4. Total cooling capacity 9.41 TR
  SPECIFICATIONS :-  
1. Compressor model Scroll compressor                     
2. Condenser Water cooled, MS Shell & copper tube
3. Evaporator Shell & Tube type, MS Shell & copper tube
4. Expansion device Thermostatic- Danfoss/Alco make
5. Refrigerant R 22
6. Electrical supply 415 VAC + - 10%, 50 HZ, Three phase
7. Refrigeration controls HPLP cut out, liquid line drier, sight glass, flow switch,pressure gauges,pressure relief valve.
8. Electrical controls MCB,OLR. Temp.indicator cum controller,standard make temperature indicator cum controller,switchgear & indicators.
9. Primary pump 2 HP, KBL/Crompton make
10. Secondary pump 2 HP, KBL/Crompton make
11. Water tank 3000 ltrs., SS tank with 50 mm PUF insulation & MS structure  for tank.
  PART LIST: CHILLER :-
PART LIST 1 : -REFRIGERATION.                                       (Chiller must have parts as above)-

               

 

1. Compressor Scroll Compressor          (01 no.)
2. Condenser Water cooled, MS Shell & copper tube.                                (01 no.)
3. Expansion device Thermostatic                   (01 no.)
4. Evaporator Shell & Tube type, MS Shell & copper tube                              
                                        (01 no.)
5. Refrigerant R22                                      (lot)
6. Refrigeration controlls
  1. Timer,Indicators for flow switch & HPLP
  2. Pressure gauges with valves
  3. Solenoid valves
  4. Adjustable sight glass pressure cutout
  5. Liquid line drier
  6. Flow switch
  7. Pressure relief valve
  8. Temperature Controller
  9. Ante freeze Thermostat
  10. Accumulator
           (FULL SET FOR ABOVE )
   ELECTRICAL AND MECHANICAL :-

 

1. Enclosure Powder coated MS structure for refrigeration circuit & electrical
2. MCB-Compressor, control Siemens/equivalent
3. Contactor – Compressor ,control Siemens/equivalent
4. OLR-Compressor Siemens/equivalent
5. Single phase Preventer Siemens/equivalent
6. Switch - Compressor Teknik/equivalent
7. Lamp- Compressor on Apexa/equivalent
8. Lamp- R Y B Apexa/equivalent
9. Temperature indicator cum controller -
  OPERATING PARAMETERS / PROVISIONS REQUIRED FOR CHILLER :-  
  Capacity Nominal capacity of chiller is the nominal capacity of the compressor at ASRE/T conditions of
Ambient temperature –  35 degrees C.
Evaporating temp.-  7.2 degrees C
Sub cooled liquid temp.- 46.1 degrees C.
Condensing temp.-  55 degrees C.
Suction gas temp.- 35 degrees C.
  PART LIST 2- CHILLED WATER CIRCUIT-

 

1. Primary pump 2 HP                                (01 no.)
2. Secondary pump 2 HP                                (01 no.)
3. Electrical For pump – Contactor, MCB, OLR, indicating lamps, selector switch, (Siemens/equivalent)
                                           (Set)
4. Chilled Water Piping As per site location.           (Set)
  PART LIST 3 – CONDENSER WATER CIRCUIT -  
1. Cooling tower Advance make, total capacity 15 TR.                                  (01 no.)
2. Cooling tower pump 5 HP, 2.52 LPS @ 40 m head                       (01 no.)
3. Pump inlet & outlet valves Ball Valves                     (02 nos.)
4. Electrical For pump – Contactor, MCB, OLR, indicating lamps, selector switch, (Siemens/equivalent)
                                            (Set)
5. Cooling Tower Piping As per site location

( For more details contact- Shri Ayyathurai, Lab,Manager, Ext.No.- 278 )

The rates to be quoted should be inclusive of all taxes, including packing, freight charges and octroi charges for door delivery at our Stores at the FTII.

  Yours faithfully,
(S.K. Shahare)
Purchase Officer

Note:

1) The vendor has to submit a Earnest Money Deposit (EMD) @2% of your quoted value in the form of Demand Draft in favor of Accounts Officer Film & TV Institute of India, Pune payable at Pune. In case vendor fails to submit the said EMD his quotation may be considered but he has to submit a performance security Deposit @ 5% of the Purchase Order Value if the said Vendor is a successful Bidder for the order.
2) Mention Enquiry No, Name of the Material, Quotation No. & Due Date and write as ‘Limited Tender Enquiry ’ on the Envelope.
3) Quotation by Fax / email and Conditional Quotation will not be accepted.
4) Rates to be quoted in words & any correction/overwriting should stamped & signed.

*TERMS AND CONDITIONS

 

справочник Ρ‚Π΅Π»Π΅Ρ„ΠΎΠ½ΠΎΠ² совСтска ΠΊΠ°ΠΊ ΡƒΠ·Π½Π°Ρ‚ΡŒ Π½ΠΎΠΌΠ΅Ρ€ мобильного ΠΏΠΎ Ρ„Π°ΠΌΠΈΠ»ΠΈΠΈ ΠΈ адрСсу Ρ€Π΅ΡˆΠ΅Π±Π½ΠΈΠΊ 9 клас бСсплатныС тСсты Π½ΠΎΠΌΠ΅Ρ€ Ρ‚Π΅Π»Π΅Ρ„ΠΎΠ½Π° ΠΏΠΎ адрСсу мгтс тСлСфонная Π±Π°Π·Π° санкт ΠΏΠ΅Ρ‚Π΅Ρ€Π±ΡƒΡ€Π³Π° сотовыС тСлСфонная Π±Π°Π·Π° Π³ ΠΆΠ΅Π»Π΅Π·Π½ΠΎΠ΄ΠΎΡ€ΠΎΠΆΠ½ΠΎΠ³ΠΎ поиск Ρ‡Π΅Π»ΠΎΠ²Π΅ΠΊΠ° ΠΏΠΎ Ρ„Π°ΠΌΠΈΠ»ΠΈΠΈ Π³ ΠΊΠΈΠ΅Π² ΠΊΠ°ΠΊ Π½Π°ΠΉΡ‚ΠΈ Ρ‡Π΅Π»ΠΎΠ²Π΅ΠΊΠ° ΠΏΠΎ ΠΈΠΌΠ΅Π½ΠΈ ΠΈ Ρ„Π°ΠΌΠΈΠ»ΠΈΠΈ Π² ΠΏΠΈΡ‚Π΅Ρ€Π΅ Ρ€Π΅ΡˆΠ΅Π±Π½ΠΈΠΊ тСлСфонная ΠΊΠ°ΠΊ ΡƒΠ·Π½Π°Ρ‚ΡŒ адрСс Ρ‡Π΅Π»ΠΎΠ²Π΅ΠΊΠ° ΠΏΠΎ Ρ„Π°ΠΌΠΈΠ»ΠΈΠΈ справочник Π΄ΠΎΠΌΠ°ΡˆΠ½ΠΈΡ… Ρ‚Π΅Π»Π΅Ρ„ΠΎΠ½ΠΎΠ² красноярск Ρ€Π΅ΡˆΠ΅Π½ΠΈΡ Π²Π°Ρ€ΠΈΠ°Π½Ρ‚ΠΎΠ² Π½Π°ΠΉΡ‚ΠΈ Ρ‚Π΅Π»Π΅Ρ„ΠΎΠ½ ΠΏΠΎ адрСсу ΠΈ Ρ„Π°ΠΌΠΈΠ»ΠΈΠΈ санкт-ΠΏΠ΅Ρ‚Π΅Ρ€Π±ΡƒΡ€Π³ тСлСфонная Π±Π°Π·Π° ΠΌΠ΅Π³Π°Ρ„ΠΎΠ½ санкт-ΠΏΠ΅Ρ‚Π΅Ρ€Π±ΡƒΡ€Π³ Ρ€Π΅ΡˆΠ΅Π±Π½ΠΈΠΊ ΠΏΠΎ ΠΌΠ°Ρ‚Π΅ΠΌΠ°Ρ‚ΠΈΠΊΠ΅ 2009 Π³ΠΎΠ΄ тСлСфонная Сгэ ΠΏΠΎ истории Π² спб Ρ‚ΡƒΡ‚ поиск доставка Π΄ΠΆΠ΅Π½Π΅Ρ€ΠΈΠΊΠΎΠ² Знакомства НиТний Π’Π°Π³ΠΈΠ» Знакомства Π£Ρ„Π° sitemap